Calorifier trouble shooting
Completion requirements
Calorifier (Steam heating) trouble shooting
Problem |
Cause |
Action |
Water temperature didn’t any rise or water temperature rice but not to reach setting |
Steam is not come |
To be supplied |
Stop valve is closed |
To be opened |
|
Defect of TRV |
Repair or renew |
|
Defect of steam trap |
Repair |
|
Strainer clogging |
To be clean |
|
Water temperature become over too high than setting |
By-pass valve is opened or leaked |
To be closed or repair/renew |
Defect of TRV |
Repair or renew |
|
Dust is bited in the seat of TRV |
To be clean |
|
Water level become too high |
Defect of ball valve |
Repair or renew |
Dust is bited in the seat of level control valve |
To be clean |
|
Valve gasket breaked |
To be change |
Last modified: Monday, 13 March 2023, 11:51 AM