Arranging the air handling unit control panel for 25% fresh air and heating
This method is applied in cases where the outdoor air quality is better than the indoor air quality, in order to reduce the indoor air CO2 amount and to increase the O2 amount, taking into account the energy saving. In such an application, command elements of the panel (Fig.20) and AHU (Fig.21) are arranged by Marine Engineer.
Figure.20 Air handling unit control panel arranged for 25% fresh air and heating
Figure.21 Air handling unit running for 25% fresh air and heating
Table.6 Command-and-control elements on panel arranged for 25% fresh air and heating
Sq. Element Setting/Monitoring Condition
1. Command Shift Power switch ON
2. Control Monitor Power lamp lits WHITE
3. Control Monitor Phase lamps lit RED, GREEN, YELLOW
4. Control Monitor Alarm lamps lit WHITE
5. Command Set control switch MAN
6. Command Set AHU start time 06h 30m
7. Command Set AHU stop time 20h 30m
8. Control Monitor outdoor air temperature 7 oC
9. Control Monitor outdoor air humidity 80%
10. Control Monitor outdoor air quality 55%
11. Command Set room thermostat temperature 23
12. Command Set room air humidity 55%
13. Command Set room thermostat air quality 80%
14. Command Set RAD 100%
15. Control RAD opens and lits 100% , GREEN
16. Command Set EAD 25%
17. Control EAD opens and lits 25% , GREEN
18. Command Set FAD 25%
19. Control FAD opens and lits 25% , GREEN
20. Command Set SAD 100%
21. Control SAD opens and lits 100% , GREEN
22. Command Set MAD 75%
23. Control MAD close and lits 75% , GREEN
24. Command Click on START button
25. Control Monitor START button lits GREEN
26. Control Monitor Aspirator voltage analog 380
27. Control Monitor Aspirator voltage digital 380
28. Control Monitor Aspirator current analog 20
29. Control Monitor Aspirator current digital 20
30. Control Monitor Aspirator speed analog 450
31. Control Monitor Aspirator speed digital 450
32. Control Monitor Ventilator voltage analog 380
33. Control Monitor Ventilator voltage digital 380
34. Control Monitor Ventilator current analog 20
35. Control Monitor Ventilator current digital 20
36. Command Set Aspr. and Vent. fan speed 45
37. Control Monitor Ventilator speed analog 450
38. Control Monitor Ventilator speed digital 450
39. Control Monitor Heating valve motor lits GREEN
40. Control Monitor Heating valve lits GREEN
41. Control Monitor Cooling valve motor lits RED
42. Control Monitor Cooling valve lits RED
43. Control Monitor Humid valve motor lits RED
44. Control Monitor Humid valve lits RED
45. Control Monitor De-humid valve motor lits GREEN
46. Control Monitor De-humid valve lits GREEN
47. Control Monitor last heating valve motor GREEN
48. Control Monitor last heating valve lits GREEN
49. Control Monitor outdoor Temperature 7
50. Control Monitor outdoor air humidity 80
51. Control Monitor outdoor air quality 55
52. Control Monitor return air temperature 18
53. Control Monitor return air humidity 70
54. Control Monitor return air quality 65
55. Control Monitor air filter-in pressure 1.1
56. Control Monitor air filter-out pressure 1.2
57. Control Monitor heating coil-in temp 15
58. Control Monitor heating coil-out temp 25
59. Control Monitor cooling coil-out temp 25
60. Control Monitor humidity 55
61. Control Monitor Supply air temperature 23
62. Control Monitor Supply air humidity 55
63. Control Monitor Supply air quality 80