Exploitation
Low temperature fresh water cooling circuit
preparation and operation procedures:
a) Make sure that the level of the FW
expansion tank is correct, top up with fresh water from the engine room if
necessary.
b) Make sure that all pressure gauges and
instrument valves in the LT cooling circuit are open.
c) Switch the valves as shown in figure below.
Example of commissioning of a low temperature fresh water cooling circuit
d) Start one LT fresh water circulation pump.
e) Turn on the overboard water cooling system if it
is not already running and supply the on-board water to the central FW cooler.
NOTE: The coolers are put into operation by
manually setting the respective inlet and outlet valves.
f) Check the system for leaks and rectify any
leaks.
g) Check the concentration level of the corrosion
inhibitors and add the chemicals required for treatment if necessary.
NOTE: To reduce the likelihood of corrosion, the
cooling water in both cooling systems is treated with inhibitory chemicals.
Cooling water shall be tested in accordance with the requirements of the
chemical supplier's and the company's operating procedures. After any necessary
chemical treatment, it is necessary to record this by indicating the amount of
chemicals added to the fresh cooling water expansion tank.
h) Check that one of the non-functioning LT FW
circulation pumps is in automatic standby mode.
NOTE: If required, the LT FW boost pump can be
switched on to boost the cooling water supply to the service group. If the
cooling demand is low, the cooling water demand can be met by using a boost
pump bypass valve and the boost pumps can be stopped.