Note the different effects of the system,
control and emergency, braking:
- Stopping the scrubber
by pressing the STOP button on the control panel: the exhaust gas cleaning
system stops in a controlled manner following a predetermined shutdown
sequence. The power supply to the exhaust gas cleaning system remains on.
- Emergency stop of the
scrubber by pressing the EMERGENCY STOP button on the control panel: the power
supply to all the main output modules of the programmable logic controllers is
switched off (only some indicators powered by the 24V backup power supply will
continue to operate). The exhaust gas purge system will stop immediately. The
power supply to the exhaust gas cleaning system remains switched on.
- After turning the MAIN
SWITCH on the control panel to the OFF position: the power supply to the
complete exhaust gas cleaning system is disconnected. Programmable logic
controllers, human machine interface displays, and data logger are disabled.
- In the event of a power
failure: the exhaust gas cleaning system stops working. 24V emergency power
supply turns on to keep programmable logic controllers, human machine interface
screens and data logger active.
Attention: A supply of sealing air must always be
available. Sealing air prevents exhaust gas from entering the scrubber when the
intake valve is closed.
Attention: Use the emergency stop button only in the
event of an accident. Never use this button to stop the system for any other
reason.