Troubleshooting for generators
Figure 100. Diode fault
SYMPTOM |
POSSIBLE CAUSE |
TEST AND REMEDIES |
Low Voltage (No Load) |
AVR “Volts” adjust incorrectly set. |
Adjust control CLOCKWISE to increase voltage. If remote hand trimmer fitted, adjust in conjunction with trimmer. |
Faulty AVR. |
Replace AVR and re-test. |
|
High Voltage (No Load) |
AVR “Volts” adjust or remote trimmer incorrectly set. |
Check and adjust as necessary. |
Low sensing supply from main stator. |
Check sensing supply with Gen. running at nominal voltage, the sensing supply should be between 190-240 volts. |
|
Faulty AVR. |
Replace AVR and re-test. |
|
Unstable Voltage (No Load) |
AVR stability control incorrectly adjusted. |
Adjust stability clockwise until voltage stabilizes. Check again on load. |
Loose or corroded connection. |
Check push on terminals on AVR. Check aux terminals for loose connections. |
|
Intermittent earth on machine. |
Megger all windings, include Exciter Stator, low insulation resistance can effect the AVR. |
|
Unbalance Voltage (No Load) |
Fault in main stator winding. |
Disconnect all external leads to Generator and re-test. A winding short will get hot, and engine will sound slightly loaded. Shut down set and check by hand for hot spots. |
No Voltage (No Load) |
Loose, broken or corroded connections. |
Check all auxiliary terminals. Check the AVR, push on terminals for tightness. Repair or renew where necessary. |
Fault PMG, stator or Rotor. |
Disconnect the PMG leads from AVR. Check voltage across leads with the set running at correct speed. |
|
Insulation failure to earth on permanent magnet stator. |
Disconnect leads and “Megger” test to earth. |
|
Main Rectifier diodes short circuit. |
Check diodes. |
Table
2. Generator Troubleshooting